Genset Specifications
GENERATOR SET SPECIFICATIONS |
|
Brand |
WEICHAI |
Model |
WPG550F8 (Open) WPG550L8 (Enclosure) |
Governor and regulation class |
In accordance to ISO 8528-5 Class G2 performance |
Phase number and connection |
3 phase, 4 wires, Y-type |
Cooling method |
Closed looped water-cooled |
Starting method |
DC 24V Electric starter |
Steady-state voltage deviation |
≤± 1% |
Steady-state frequency band |
≤± 1% |
Engine Specifications
ENGINE |
||
Brand |
|
WEICHAI |
Model |
|
WP13D490E310 |
Gross Power |
kWm |
ESP - 490 / PRP - 450 |
Cylinder / Type / Aspiration |
|
6 / In-line / Turbocharged and Aftercooled |
Bore x Stroke |
mm |
127 x 165 |
Displacement |
L |
12.54 |
Compression ratio |
|
15.2:1 |
Brake Mean Effective Pressure |
kPa |
ESP – 3126 |
Governor |
|
Electronic |
Alternator Specifications
ALTERNATOR |
|
Brand |
WEICHAI |
Model |
WHA-500-4/0.4 |
Coupling / No. of Bearing |
Direct / Single |
Type of Excitation |
Self-excitation |
Cooling type |
Air |
Voltage regulation method |
AVR |
Insurance |
Class H |
Temperature rise |
Class H |
Protection Grade |
IP23 |
Efficiency at 0.8p.f.@100% load |
94.4% |
I. COOLING SYSTEM:
COOLING SYSTEM |
||
Type of Coolant |
|
Liquid (water + 50% antifreeze) |
Total Cooling System Capacity (with Radiator) |
L |
62 |
Max coolant temperature – shutdown |
°C |
105 |
Cooling Fan Airflow |
m3/min |
474 |
II. LUBRICATION SYSTEM:
LUBRICATION SYSTEM |
||
Operating Temperature range before Engine |
°C |
78 -105 |
Oil consumption |
g/kW.hr |
≤ 0.2% |
Total lub oil capacity (including filters) |
L |
38 |
Type of lub oil filter |
|
Spin-on full flow filter |
III. EXHAUST SYSTE:
EXHAUST SYSTEM |
|||
Exhaust Gas temperature after the turbocharger |
°C |
580 |
|
Exhaust Gas flow |
m3/min |
ESP – 114.8 |
PRP – 102.3 |
Max Exhaust back pressure |
mBar |
120 |
|
IV. FUEL SYSTEM:
FUEL SYSTEM |
|||
Type of fuel filter |
|
|
Spin-on fuel flow filter |
Min. internal diameter of the supply pipe |
mm |
|
14 |
Min. internal diameter of the return pipe |
mm |
|
14 |
Max fuel return restriction |
Bar |
|
0.5 |
Max. fuel inlet temperature |
°C |
|
50 |
Fuel supply flow |
L/hr |
|
400 |
Fuel Consumption (Tolerance +3%) Rating |
|
gr/kWh |
L/hr |
100%ESP |
|
211 |
123.1 |
100%PRP |
|
204.3 |
109.5 |
75%PRP |
|
187.3 |
75.3 |
50%PRP |
|
190.5 |
51 |
25%PRP |
|
207.5 |
27.8 |
Main / Emergency Generator sets for Data Centers, Residential Building, Shopping Mall, Hospitals, Industrial Parks, Farms, Mining areas...